Menu Structure

1.0 Operation Mode             1.1 left to escape, right to continue to prevent accidental mode switching

1.2 User Mode
  1. ELC
  2. IGC
  3. Protection Relay
  4. User Load
  5. Output Test


1. for sychronous Generators
2. for Induction Generators
3. emergency fault shutdown
4. automatic user load warning and switching
5. Output Test Mode switches all outputs on,
    regardless of input values

1.3 single phase/3phase

1.4 up one level



2.0 Input Readings 2.1 Hz

2.2 AC Volts L1 L2 L3

2.3 DC Volts for checking a backup battery to operate the water valves in case of power outage

2.4 current amps

2.5 Dump load percentage how much of the dumpload is currently on




2.6 shutdown reason

2.7 total operating days while all values are in range. write to eeprom every day and while shutdown

2.8 operating days since last shutdown "

2.9 reset total operating days

2.10 one level up



3.0 Range Settings
For fault detection




3.1 minimum frequency

3.2 maximum frequency




3.3 Minimum AC Voltage

3.4 Maximum AC Voltage

3.5 Minimum DC Voltage

3.6 Maximum DC Voltage

3.7 maximum amps

3.8 delay time for how long must the value be permanently out of range to trigger shutdown




3.9 up to top menu



4.0 ELC/IGC Settings 4.1 ELC: target frequency 50 or 60 Hz

4.2: IGC: target voltage 220, 230, or 240 Volt (depending on your country)

4.3 P-Value see here

4.4 I-Value

4.5 Valve ON /secs in case the valves operate very quickly, one can
specify a run (ON) / wait (OFF) time here to slow the change rate down and avoid oscillation

4.6 Valve OFF /secs

4.7 up to top menu



5.0 Protection Relay start up/fault reset Main relay/connector will be released as soon as all values are in the green range.
If there is a water valve relay, it will be released even if there is no Mains Voltage.












6.0 User Load Settings


6.1 Back on Voltage hysteresis, after user load has been disconnected

6.2 Back on frequency hysteresis, after user load has been disconnected

6.3 delay time before off The first relay will switch immediately, this can be use for a warning signal.
The second relay will switch after the time specified here.

6.4 delay time before back on This gives the users time to disconnect appliances before the cotroller tries to reconnect.

6.5 overload warning signal When activated, this will regularly switch on some dumpload in case of underfrequency/undervoltage. the resulting frequency drop will change the sound of the hum in user appliances. If they hear this, they should switch off loads.

6.6 up one level



7.0 Calibration
Adjust meter readings

7.1 Line 1 correction factor

7.2 Line 2 correction factor

7.3 Line 3 correction factor

7.4 DC correction factor

7.5 Amps correction factor

7.6 P-I Auto Tuning not implemented

7.7 software/hardware version mention this in communication for problem tracing




7.8 up one level