| 1.0 Operation Mode | 1.1 left to escape, right to continue | to prevent accidental mode switching |
1.2 User Mode
|
1. for sychronous Generators 2. for Induction Generators 3. emergency fault shutdown 4. automatic user load warning and switching 5. Output Test Mode switches all outputs on, regardless of input values |
|
| 1.3 single phase/3phase | ||
| 1.4 up one level | ||
| 2.0 Input Readings | 2.1 Hz | |
| 2.2 AC Volts L1 L2 L3 | ||
| 2.3 DC Volts | for checking a backup battery to operate the water valves in case of power outage | |
| 2.4 current amps | ||
| 2.5 Dump load percentage | how much of the dumpload is currently on | |
| 2.6 shutdown reason | ||
| 2.7 total operating days and hours | while all values are in range. write to eeprom every day and while shutdown | |
| 2.8 reset total operating time | " | |
| 2.9 operating time since last shutdown | ||
| 2.10 one level up | ||
| 3.0 Range Settings | For fault detection | |
| 3.1 minimum frequency | ||
| 3.2 maximum frequency | ||
| 3.3 Minimum AC Voltage | ||
| 3.4 Maximum AC Voltage | ||
| 3.5 Minimum DC Voltage | ||
| 3.6 Maximum DC Voltage | ||
| 3.7 maximum amps | ||
| 3.8 delay time | for how long must the value be permanently out of range to trigger shutdown | |
| 3.9 up to top menu | ||
| 4.0 ELC/IGC Settings | 4.1 ELC: target frequency | 50 or 60 Hz |
| 4.2: IGC: target voltage | 220, 230, or 240 Volt (depending on your country) | |
| 4.3 P-Value | see here | |
| 4.4 I-Value | ||
| 4.5 Valve ON /secs | in case the valves operate very quickly, one can specify a run (ON) / wait (OFF) time here to slow the change rate down and avoid oscillation |
|
| 4.6 Valve OFF /secs | ||
| 4.7 up to top menu | ||
| 5.0 Protection Relay | start up/fault reset | Main relay/connector will be released as soon as all values are in the green range. If there is a water valve relay, it will be released even if there is no Mains Voltage. |
| 6.0 User Load Settings | ||
| 6.1 Back on frequency | hysteresis, after user load has been disconnected | |
| 6.2 Back on Voltage | hysteresis, after user load has been disconnected | |
| 6.3 delay time in sec. before off | The first relay will switch immediately, this can be used for a warning signal. The second relay will switch after the time specified here. |
|
| 6.4 delay time in sec. before back on | This gives the users time to disconnect appliances before the controller tries to reconnect. | |
| 6.5 overload warning signal | When activated, this will regularly switch on some dumpload in case of underfrequency/undervoltage. the resulting frequency drop will change the sound of the hum in user appliances. If they hear this, they should switch off loads. | |
| 6.6 up one level | ||
| 7.0 Calibration | Adjust meter readings | |
| 7.1 Line 1 correction factor | ||
| 7.2 Line 2 correction factor | ||
| 7.3 Line 3 correction factor | ||
| 7.4 DC correction factor | ||
| 7.5 Amps correction factor | ||
| 7.6 P-I Auto Tuning | not implemented | |
| 7.7 software/hardware version | mention this in communication for problem tracing | |
| 7.8 up one level | ||
Menu Structure